ABB REC670 Bay Control IED 1MRK002814-AC | 1MRK002800-AB

Condition: New

Live Support
  • 100% SECURED PAYMENTS
  • AVAILABLE IN STOCK - READY TO SHIP
  • EXPRESS DELIVERY: WORLDWIDE DELIVERY BY FEDEX & DHL EXPRESS COURIER
  • HASSLE FREE 14-DAY RETURNS
NDMARINETECH PAYMENT OPTIONS
Description

ABB REC670 Bay Control IED (MPN: 1MRK002814-AC | 1MRK002800-AB)

The ABB REC670 (referencing hardware assembly/order designators 1MRK002814-AC and 1MRK002800-AB) is a numerical bay control, monitoring, and backup protection Intelligent Electronic Device (IED) within the ABB Relion® 670 series. Engineered for medium- and high-voltage switchgear bays, offshore platforms, and high-voltage marine propulsion switchboards, the unit executes bay-level interlocking, synchrocheck (ANSI 25), auto-reclosing (ANSI 79), and multi-breaker apparatus control.

The REC670 utilizes a modular 19-inch rack architecture (available in 1/2, 3/4, or 1/1 x 19-inch cases). This allows electrical and marine engineers to populate rear slots with dedicated Transformer Input Modules (TRM), Binary Input Modules (BIM), Binary Output Modules (BOM), Static Output Modules (SOM), and Combined Input/Output Modules (IOM) tailored to single-breaker, double-breaker, or 1½-breaker busbar topologies.

 

Model Details

  • Product Series: ABB Relion® 670 Series (Bay Control IED)
  • Primary Model: REC670
  • Primary MPN / Order Code: 1MRK002814-AC
  • Associated Assembly / Variant MPN: 1MRK002800-AB (Base hardware/order code variant within the REC670 platform family)
  • Country of Origin: Sweden (ABB Substation Automation Products, Västerås)

 

Features

  1. Multi-Breaker Bay Control & Interlocking: Pre-configured logic templates handle up to 1½-breaker diameters, double-busbar switching, and apparatus position supervision with built-in synchrocheck (ANSI 25) and auto-reclosing (ANSI 79).
  2. High-Speed IEC 61850 GOOSE Messaging: Executes peer-to-peer horizontal interlocking and breaker failure trip commands over redundant 100BASE-FX optical fiber ports without hardwired inter-panel copper.
  3. Modular Hardware & Slot Scalability: Accepts up to 14 BIMs or 6 IOMs in a full 1/1 x 19-inch chassis, allowing field expansion of binary/analog channel counts without replacing the main CPU.
  4. Integrated 40-Channel Disturbance Recorder: Records high-resolution pre-fault and post-fault oscillography across 40 analog and 96 binary channels for rapid root-cause diagnostics.
  5. Comprehensive Backup Protection Suite: Incorporates four-step directional phase/residual overcurrent (51/67, 51N/67N), sensitive directional earth-fault (67N) for isolated/high-impedance marine networks, and breaker failure protection (50BF).

 

ABB REC670 Bay Control IED Technical Specifications (1MRK002814-AC / 1MRK002800-AB)

Parameter Specification / Rating
Manufacturer ABB (Relion 670 Series / Hitachi Energy)
Model & Part Numbers REC670 | MPN: 1MRK002814-AC / 1MRK002800-AB
Auxiliary Power Supply (Slot X11) 24–60 V DC (±20%) or 90–250 V DC (±20%) depending on PSM variant
Rated Current Inputs (TRM) 1 A or 5 A RMS (50/60 Hz); Operating Range: (0–100) × Ir
Current Thermal Withstand 100 × Ir for 1 s (350 A max with COMBITEST); 30 × Ir for 10 s; 4 × Ir continuous
Current Input Burden < 20 mVA at Ir = 1 A; < 150 mVA at Ir = 5 A
Rated Voltage Inputs (TRM) 110 V or 220 V AC RMS; Operating Range: 0–340 V; Withstand: 420 V continuous / 450 V (10 s)
Voltage Input Burden < 80 mVA at 220 V
Binary Input Modules (BIM / IOM) 16 channels per BIM / 8 per IOM; 24/30 V, 48/60 V, 110/125 V, 220/250 V DC; 3 ms operate time (5 ms debounce for surge compliance)
Binary Output Modules (BOM / IOM / SOM) High-duty trip/signaling contacts; max 2 relays per module continuously energized
Rear Terminal Slot Allocation X11: PSM | X31–X162: BIM, BOM, IOM, SOM, MIM | X401/X411: TRM
Communication Protocols IEC 61850-8-1 (GOOSE, MMS), IEC 60870-5-103, DNP3.0, LON, SPA, IEEE C37.118
Optical Fiber Interface IEEE 802.3u 100BASE-FX, 62.5/125 µm multimode, 1300 nm wavelength
Disturbance Recorder Capacity Up to 40 analog channels and 96 binary channels
Operating Temperature -25°C to +55°C continuous (-40°C to +70°C storage)
Certifications & Standards IEC 60255, IEC 61850, DNV Offshore / DNV GL (1418-18), IEEE C37.90, UL E502400, CE

Applications

  • Marine High-Voltage (HV) Main Switchboards: Generator synchronization, bus-tie breaker interlocking, and feeder protection on diesel-electric propulsion vessels, FPSOs, and drillships.
  • Offshore Substations & Wind Platforms: Bay-level control and IEC 61850 SCADA integration for offshore converter stations and collector switchgear.
  • Utility Transmission & Distribution Substations: Control and backup protection for single-bus, double-bus, and 1½-breaker bay configurations.
  • Heavy Industrial Power Plants: Steelworks, petrochemical refineries, and captive cogeneration powerhouses requiring deterministic load-shedding and transformer bay control.

 

Compatibility

  • Engineering & Configuration Software: Configured via ABB PCM600 (Protection and Control IED Manager) using IEC 61850 SCL (SCD/CID/ICD) files.
  • Compatible Relion 670 Series IEDs: Directly interoperable via GOOSE and MMS with RED670 (Line Differential), REL670 (Line Distance), RET670 (Transformer Protection), and REB670 (Busbar Protection).
  • Remote I/O & Merging Units: Compatible with ABB RIO600 remote I/O units and SAM600 process bus merging units.
  • Test Switch Compatibility: Engineered for flush/rack mounting alongside ABB COMBITEST RTXP 18 / RTXP 24 test switches for safe secondary injection testing.

 

Part Number Cross-References

  • 1MRK002814-AC: REC670 Bay Control IED (Standard Hardware/Revision C designation)
  • 1MRK002800-AB: REC670 Base Hardware Assembly / Pre-configured Order Variant
  • 1MRK002814-AB / 1MRK002814-AG: Preceding and succeeding hardware revision suffixes for the REC670 platform (verify firmware version 1.2 vs. 2.1/2.2 before cross-swapping)
  • 1MRK004814-AC: Later-generation REC670 firmware/hardware frame variant (Version 2.2x)

 

Frequently Asked Questions

What is the difference between ABB 1MRK002814-AC and 1MRK002800-AB?

Both part numbers belong to the ABB Relion REC670 Bay Control IED platform. 1MRK002800-AB represents the base hardware/order configuration designator, whereas 1MRK002814-AC denotes a specific factory hardware/firmware revision assembly. When replacing an existing unit, always verify the exact rear module slot configuration (TRM, PSM, BIM, BOM) and firmware version (e.g., v1.2, v2.1, or v2.2) to ensure direct drop-in compatibility.

Is the ABB REC670 approved for marine and offshore switchboard installations?

Yes. The REC670 carries DNV Offshore / DNV GL type approval (Certificate Ref. 1418-18) alongside full IEC 60255 environmental, vibration, and electromagnetic compatibility (EMC) compliance. It is widely deployed on high-voltage marine propulsion switchboards, offshore wind platforms, and FPSOs.

Can the ABB REC670 1MRK002814-AC be hot-swapped while the switchgear bay is live?

No. The REC670 is not designed for live hot-swapping. Removing the chassis or rear terminal blocks while primary circuits are energized will open-circuit current transformers (creating lethal high-voltage spikes) and cause uncontrolled breaker trips. Always isolate DC control power, insert the COMBITEST test handle to short CT secondaries and isolate trip outputs, and back up the PCM600 configuration file before removing hardware.

How are the rear terminal slots allocated on the REC670?

Rear hardware slots follow a fixed physical addressing scheme: X11 houses the Power Supply Module (PSM); X31 through X162 (depending on 1/2, 3/4, or 1/1 x 19-inch rack width) house binary and mA I/O modules (BIM, BOM, IOM, SOM, MIM); and X401 / X411 house the analog Transformer Input Modules (TRM) for CT and VT connections.

Which software is required to configure and download settings to the REC670?

Configuration, graphical logic programming (ACT), IEC 61850 GOOSE engineering, and disturbance record extraction are performed using ABB PCM600 (Protection and Control IED Manager) via the front RJ45 engineering port or rear station bus Ethernet ports.

Shipping and Delivery

14 DAYS RETURN POLICY

RETURNS ARE ACCEPTED IN 14 DAYS. BUYER PAYS THE SHIPPING CHARGES. RESTOCKING FEES 20%.

NOTE:

IF THE ITEM COMES UNDER CUSTOMS, THE BUYER WILL BE FULLY RESPONSIBLE FOR DUTIES AND OTHER CHARGES. WE, AS THE SELLER, DO NOT ACCEPT RETURNS OR REFUNDS IN THIS CASE. KINDLY CONNECT WITH US BEFORE PURCHASING AN ITEM OR IF YOU HAVE ANY OTHER QUERIES.

FEEDBACK

WE WILL BE WAITING FOR YOUR VALUABLE FEEDBACKS. THANK YOU FOR SHOWING TRUST IN US.

100% Genuine Products

-> YOU WILL GET WHAT YOU SEE IN PHOTOS

-> UNDERSTAND THE PRODUCT BEFORE BUYING

PACKAGING

QUALITY PACKING FOR EACH PRODUCT. ASSURED SAFE & UNDAMAGED DELIVERY.

SHIPPING

FeDEX, DHL EXPRESS INTERNATIONAL SHIPPING.

TAXES & IMPORT DUTIES

DESTINATION COUNTRY ALL TAXES & DUTY TO BE PAID BY BUYER (NOT INCLUDED IN PRICE.