ABB Sace Megamax F4S 3200A Air Circuit Breaker (690V)
The ABB Sace Megamax F4S 3200A is a heavy duty, high performance Air Circuit Breaker (ACB) designed for the high electrical requirements of large scale industrial infrastructures and marine main switchboards. This legacy breaker is rated for 690V AC and continuous current rated for 3200A and is a famous “S-Class” (Standard/High selected breaking performance) breaker that provides premium thermal and short-circuit protection. The SACE PR1/P (LSIG parameters) modern electronic trip devices ensure complete accuracy in selective coordination, safeguarding heavy machinery, alternators and main distribution lines from catastrophic faults.
Model Details:
- Model Range: SACE Megamax F Series (Frame 4)
- Specific Model: ABB Sace Megamax F4S 3200
- Manufacturer Part Number (MPN): F4S3200
Specifications: F4S3200
| Feature / Parameter | Specification Details |
|---|---|
| Manufacturer | ABB (Asea Brown Boveri) |
| Frame Size | F4 (Frame 4) |
| Rated Continuous Current (In / Iu) | 3200 Amps |
| Rated Operational Voltage (Ue) | 690V AC (50/60 Hz) |
| Breaking Capacity Performance | S-Class (High Selectivity / Standard Industrial) |
| Number of Poles | 3-Pole (3P) / 4-Pole (4P) available depending on configuration |
| Electronic Protection Unit | SACE PR1/P (LSIG: Long, Short, Instantaneous, Ground fault) |
| Control Unit Complement | PR1/C |
| Mounting Configuration | Fixed (F) or Draw-out / Withdrawable (W) configurations available |
| Approximate Weight | ~230 lbs / 104 kg |
Applications
- Marine Main Switchboards Main generator or bus-tie breaker for commercial boats, container ships and offshore drilling platforms.
- Industrial Power Distribution Used in large manufacturing industries, steel mills, automotive factories to protect key low voltage substations.
- Critical Infrastructure & Data Centers Robust incoming power protection for high capacity step-down transformers.
- Power Plants & Utilities: Executed as a point of execution for generator protection and grid synchronization panels.
Compatibility
- System Integration: Compatible with classic low-voltage ABB Sace power distribution switchgear panels from the 1990s through mid-2000s legacy eras.
Part Number Cross-References
- Cross-References / Direct Replacement Path: * Direct legacy equivalents: Megamax F4S 3200 PR111, PR112, or PR113 series.
Maintenance Guide by NDMarineTech:
- PR1/P Battery Lifespan: The internal microprocessor trip units rely on auxiliary power during operation, but internal memory can suffer if stored dead. Always test the electronic trip unit with a secondary injection test kit before racking a long-stored surplus unit back into service.
- Contact Resistance Checks: Before installation, check the micro-ohm drop across the main contacts. For a 3200A breaker, any high resistance reading indicates contact pitting or weak spring pressure, which will cause thermal runaway at full load.
- Arc Chute Inspection: Never put a surplus or reconditioned breaker into service without removing the arc chutes to visually inspect the main and arcing contacts for erosion.
14 DAYS RETURN POLICY
RETURNS ARE ACCEPTED IN 14 DAYS. BUYER PAYS THE SHIPPING CHARGES. RESTOCKING FEES 20%.
NOTE:
IF THE ITEM COMES UNDER CUSTOMS, THE BUYER WILL BE FULLY RESPONSIBLE FOR DUTIES AND OTHER CHARGES. WE, AS THE SELLER, DO NOT ACCEPT RETURNS OR REFUNDS IN THIS CASE. KINDLY CONNECT WITH US BEFORE PURCHASING AN ITEM OR IF YOU HAVE ANY OTHER QUERIES.
FEEDBACK
WE WILL BE WAITING FOR YOUR VALUABLE FEEDBACKS. THANK YOU FOR SHOWINGÂ TRUSTÂ INÂ US.
100% Genuine Products
-> YOU WILL GET WHAT YOU SEE IN PHOTOS
-> UNDERSTAND THE PRODUCT BEFORE BUYING
PACKAGING
QUALITY PACKING FOR EACH PRODUCT. ASSURED SAFE & UNDAMAGED DELIVERY.
SHIPPING
FeDEX, DHL EXPRESS INTERNATIONAL SHIPPING.
TAXES & IMPORT DUTIES
DESTINATION COUNTRY ALL TAXES & DUTY TO BE PAID BY BUYER (NOT INCLUDED IN PRICE.