GE Fanuc IC693CPU374-KZ Series 90-30 CPU 374 Plus 240KB Ethernet PLC Processor

The GE Fanuc IC693CPU374-KZ is a single-slot central processing unit designed for the Series 90-30 programmable logic controller architecture. Built around a 133 MHz 586-class embedded microprocessor, it provides 240 KB of configurable user memory and an integrated 10/100 Mbps two-port auto-sensing Ethernet switch. This module serves as the primary logic engine for mid-to-large discrete and process automation systems, executing Boolean logic at a typical scan rate of 0.15 milliseconds per 1K of logic.

The IC693CPU374-KZ eliminates the need for separate rack-mounted Ethernet interface modules (such as the IC693CMM321), freeing up backplane slots for critical I/O. The -KZ hardware and firmware revision ships with CPU Firmware Version 12.71 and Ethernet Firmware Version 6.20, adding Simple Network Time Protocol (SNTP) support for local time zones and daylight saving time adjustments—a critical requirement for synchronized vessel alarm logging and voyage data recorder (VDR) time-stamping.

 

Model Details

  • Manufacturer Part Number (MPN): IC693CPU374-KZ
  • Base Catalog Number: IC693CPU374
  • Product Line: Series 90-30 (CPU 374 Plus)
  • Firmware Revision (-KZ): CPU Firmware v12.71 / Embedded Ethernet Firmware v6.20
  • Form Factor: Single-slot module (installs exclusively in Slot 1 of a Series 90-30 CPU baseplate)
  • PCB Assembly Reference: 44A752486-G01 / 44A752487-001

 

Features

  1. High-Speed 133 MHz 586 Processor: Executes Boolean contacts at 0.15 ms per 1K instructions and includes hardware-based floating-point math for rapid PID loop calculations in engine governor and cargo pump control.
  2. Dual-Port Embedded 10/100Base-T/TX Switch: Features two front-facing RJ-45 ports sharing a single IP address with auto-sensing speed, duplex, and MDI/MDI-X crossover detection for daisy-chained HMI and SCADA topologies.
  3. 240 KB Configurable User Memory: Allocates memory dynamically across program logic, registers (%R), analog inputs (%AI), and analog outputs (%AQ) up to 32,640 words each, alongside 2,048 discrete inputs (%I) and 2,048 discrete outputs (%Q).
  4. Multi-Protocol Industrial Ethernet: Supports simultaneous SRTP (Service Request Transport Protocol) client/server channels, Ethernet Global Data (EGD) periodic exchanges, and Modbus/TCP client/server (Conformance Classes 0, 1, and 2).
  5. SNTP Time Synchronization (KZ Revision): Firmware v6.20 enables precise network clock synchronization with local time zone offsets, ensuring accurate sequence-of-events timestamps across distributed shipboard alarm panels.

 

Technical Specifications

Specification Parameter Technical Rating / Value
Manufacturer / Brand GE Fanuc / GE Intelligent Platforms (Emerson)
Catalog Number / MPN IC693CPU374-KZ (Base: IC693CPU374)
Firmware Version CPU Firmware v12.71 / Ethernet Firmware v6.20
Processor Architecture 133 MHz Embedded 586 Microprocessor with Hardware Floating-Point Math
Boolean Scan Rate 0.15 ms per 1K Boolean logic
Total User Memory 240 KB (245,760 Bytes) Configurable RAM / Flash
Discrete I/O Capacity 2,048 Inputs (%I) / 2,048 Outputs (%Q)
Analog & Register Memory 128 to 32,640 words each for %R, %AI, and %AQ
Ethernet Interface 2x RJ-45 10/100Base-T/TX Auto-Sensing Ports (Built-in Switch, Single IP)
Supported Ethernet Protocols SRTP Client/Server, Ethernet Global Data (EGD), Modbus/TCP Client/Server, SNTP
Serial / Diagnostic Ports 1x RJ-11 RS-232 Station Manager Port; SNP/SNPX via Power Supply RS-485 Port
Backplane Power Consumption 7.4 Watts (1.48 A @ +5 VDC)
Baseplate Expansion Up to 8 Baseplates (1 CPU Baseplate + 7 Expansion/Remote Racks)
Operating Temperature 0°C to 60°C (32°F to 140°F)
Storage Temperature -40°C to 85°C (-40°F to 185°F)
Certifications & Approvals UL 508, cUL Class I Div 2 (Groups A, B, C, D), CE, ATEX Zone 2 (II 3 G EEx nA IIC T5)

 

Compatibility

  • Compatible Baseplates: Must be installed in Slot 1 of a Series 90-30 modular CPU baseplate, including IC693CHS391 (10-slot), IC693CHS392 (10-slot expansion), IC693CHS397 (5-slot), or IC693CHS398 (5-slot). Not compatible with embedded CPU baseplates (IC693CPU311/313/323).
  • Required High-Capacity Power Supplies: Due to the 7.4 W (+5 VDC) load of the CPU374 Plus, standard 15W power supplies (such as IC693PWR321) are insufficient when populated with I/O modules. Pair exclusively with 30W High-Capacity Power Supplies:
    • IC693PWR330: 120/240 VAC or 125 VDC input, 30W output
    • IC693PWR331: 24 VDC input, 30W output (standard for 24V marine engine room control consoles)
    • IC693PWR332: 12 VDC input, 30W output
  • Compatible Programming Software:
    • Proficy Machine Edition (PME) Logic Developer-PLC (v5.0 or higher recommended for full -KZ SNTP feature configuration)
    • CIMPLICITY Machine Edition Logic Developer v2.60 or later
    • VersaPro v2.03 or later (Note: Hand-Held Programmer IC693PRG300 is not supported)
  • Compatible Accessories:
    • IC693ACC302: Auxiliary High-Capacity Battery Module (extends RAM retention from 1.2 months to 15 months)
    • IC200ACC003: E-Z Program Store Device (allows firmware/logic upload without a PC)
    • IC693CBL316A: RS-232 Station Manager Serial Cable (RJ-11 to DB-9)
    • IC690ACC901: Miniconverter Kit for serial programming via power supply RS-485 port

 

Applications

  • Marine Main & Auxiliary Engine Monitoring: High-speed polling of exhaust gas temperatures, lube oil pressures, and jacket water cooling loops via analog input modules (IC693ALG222/223) with Modbus/TCP forwarding to the bridge Integrated Automation System (IAS).
  • Ballast Water & Cargo Pump Control: Deterministic valve sequencing and tank level gauging across up to 8 distributed baseplates in tanker and bulk carrier pump rooms.
  • Power Management Systems (PMS): Generator load sharing, synchronizer interfacing, and heavy-consumer preferential tripping using hardware floating-point math.
  • Water & Wastewater Treatment Plants: Telemetry and SCADA integration over Ethernet Global Data (EGD) and SRTP without external protocol gateways.
  • Oil & Gas Skid Packages: Class I, Division 2 / ATEX Zone 2 compliant compressor and separator control skids.

 

Frequently Asked Questions

What is the difference between the IC693CPU374-KZ and earlier revisions like IC693CPU374-JY or IC693CPU374-GS?

The IC693CPU374-KZ is a later production hardware and firmware revision running CPU Firmware v12.71 and Ethernet Firmware v6.20. While physically and electrically identical to earlier -JY and -GS revisions, the -KZ firmware adds SNTP support for local time zone offsets and daylight saving time. It is a direct drop-in replacement for all earlier IC693CPU374 suffixes.

Does the IC693CPU374-KZ have built-in serial ports for SNP programming?

No. The faceplate of the IC693CPU374-KZ features two RJ-45 Ethernet ports and one RJ-11 RS-232 Station Manager diagnostic port. If you need to program the PLC or communicate over SNP/SNPX serial protocols, you must connect to the 15-pin RS-485 serial port located on the Series 90-30 rack power supply using an IC690ACC901 serial converter cable.

Can the two Ethernet ports on the IC693CPU374-KZ be assigned different IP addresses for network redundancy?

No. Both 10/100Base-T/TX RJ-45 ports are bridged internally through a built-in auto-sensing Ethernet switch and share a single IP address and MAC address. They are designed to eliminate external mini-switches when daisy-chaining local HMIs or programming terminals, not for dual-homed subnet isolation.

How much memory does the IC693CPU374-KZ provide for ladder logic and registers?

The module includes 240 KB (245,760 bytes) of total user memory shared between executable logic and configurable data tables. You can configure %R (registers), %AI (analog inputs), and %AQ (analog outputs) from 128 up to 32,640 words each, alongside fixed capacities of 2,048 discrete inputs (%I) and 2,048 discrete outputs (%Q).

Is the IC693CPU374-KZ certified for hazardous locations on offshore vessels and rigs?

Yes. The module carries UL 508 and cUL listings for Class I, Division 2, Groups A, B, C, and D hazardous locations (T4A), as well as ATEX Zone 2 (II 3 G EEx nA IIC T5) certification for ambient temperatures from 0°C to 60°C.

Shipping and Delivery

14 DAYS RETURN POLICY

RETURNS ARE ACCEPTED IN 14 DAYS. BUYER PAYS THE SHIPPING CHARGES. RESTOCKING FEES 20%.

NOTE:

IF THE ITEM COMES UNDER CUSTOMS, THE BUYER WILL BE FULLY RESPONSIBLE FOR DUTIES AND OTHER CHARGES. WE, AS THE SELLER, DO NOT ACCEPT RETURNS OR REFUNDS IN THIS CASE. KINDLY CONNECT WITH US BEFORE PURCHASING AN ITEM OR IF YOU HAVE ANY OTHER QUERIES.

FEEDBACK

WE WILL BE WAITING FOR YOUR VALUABLE FEEDBACKS. THANK YOU FOR SHOWING TRUST IN US.

100% Genuine Products

-> YOU WILL GET WHAT YOU SEE IN PHOTOS

-> UNDERSTAND THE PRODUCT BEFORE BUYING

PACKAGING

QUALITY PACKING FOR EACH PRODUCT. ASSURED SAFE & UNDAMAGED DELIVERY.

SHIPPING

FeDEX, DHL EXPRESS INTERNATIONAL SHIPPING.

TAXES & IMPORT DUTIES

DESTINATION COUNTRY ALL TAXES & DUTY TO BE PAID BY BUYER (NOT INCLUDED IN PRICE.