New Sealed Honeywell FC‑RUSIO‑3224 Remote Universal Safe I/O Module
$5,899.00
Condition: New – Seal Pack
1 in stock
Make an Offer
The Honeywell FC-RUSIO-3224 is a 32-channel Remote Universal Safe I/O module that is redundant and may be used with the Honeywell Safety Manager and Safety Manager SC designs. The module is a key part of SIL 3 (Safety Integrity Level 3) loops. It connects field sensors and actuators to the central safety controller using the SafeNet high-speed redundant Ethernet infrastructure. Each of the 32 channels may be set up in software, so you can process digital input (DI), digital output (DO), analog input (AI), or analog output (AO) data without having to alter the hardware terminals.
The FC-RUSIO-3224 is made to maintain the signal clean even when there is a lot of total harmonic distortion (THD) and voltage spikes, which happen a lot in 60Hz isolated shipboard grids. The galvanic isolation and electromagnetic compatibility (EMC) ratings keep the low-voltage logic apart from the inductive spikes and 440V distribution noise in the engine room. The module’s conformal coating keeps it safe from the rapid oxidation and electrolyte leaks that happen in places with a lot of salt and humidity, like the engine room or mid-ship.
Model Details
- Brand: Honeywell
- Model Number: FC-RUSIO-3224
- MPN (Manufacturer Part Number): FC-RUSIO-3224
- Product Type: Remote Universal Safe I/O Module (32-Channel, 24 VDC)
- Design Generation: Series C Compatible
- Hardware Revision Stability: Compatible across core Safety Builder software revisions.
Technical Specifications: FC-RUSIO-3224
| Parameter | Rated Value / Engineering Data |
|---|---|
| Number of Channels | 32 Universal Safety I/O Channels (Configurable via Safety Builder) |
| Nominal Supply Voltage | 24 VDC (-15% to +30% voltage tolerance limits) |
| Internal Module Current Drain | Maximum 300 mA (quiescent consumption, excluding external loop load) |
| Maximum Combined Total Field Load | 9.0 Amperes continuous aggregate current capability |
| Channel Configuration Types | Digital Input (DI), Digital Output (DO), Analog Input (AI), Analog Output (AO) |
| Digital Input Parameters | 24 VDC PNP/NPN dry contact configurations with optional loop fault monitoring |
| Digital Output Parameters | 24 VDC sourcing with comprehensive short-circuit and open-loop line monitoring |
| Analog Input Range | 0–20 mA or 4–20 mA active source signaling with integrated loop diagnostics |
| Analog Output Range | 0–20 mA or 4–20 mA active loops with open-circuit detection (Up to 16 concurrent AO channels) |
| Maximum Field Capacitance | 100 nF for standard AI/DI/AO channels; up to 1 µF for dedicated DO configurations |
| Safety Integrity Rating | SIL 3 compliant per IEC 61508 / IEC 61111 certifications |
| Communication Interface | Dual 100Mbaud Ethernet links over Safety Manager Universal I/O protocol; supports HART pass-through |
| Sequence of Events (SOE) Accuracy | Integrated real-time clock yielding 1 millisecond time-stamping resolution |
| Overvoltage / Polarity Defense | Parallel diode integration engineered to trigger high-speed protective fuses |
| Environmental Operating Bounds | Surrounding External Air: -40°C to +70°C (-40°F to +158°F); Internal Core Sensor: -40°C to +90°C |
| Relative Humidity Limit | 10% to 95% non-condensing relative operating humidity |
| Pollution Severity Grade | Pollution Degree 2 or cleaner environmental placement |
| Physical Unit Footprint | 145.0 mm x 165.1 mm x 72.4 mm (Height x Width x Depth) |
| Net Unit Weight | Approximately 0.66 kg to 0.70 kg (1.45 lbs to 1.54 lbs) |
Honeywell FC-RUSIO-3224 Function and Design
- The FC-RUSIO-3224 is a universal safe I/O device with 32 channels that works with 24 V DC. You can set up each channel as a digital input, digital output, analogue input, or analogue output, depending on what the application demands.
- Honeywell Safety Builder software and Safety Manager handle the setup and safety logic, so the module can be used in safety instrumented functions that satisfy IEC 61508/61511 requirements up to SIL 3.
- The module is one of Honeywell’s Series C hardware products. You put it on a separate I/O Termination Assembly (IOTA) that connects the field wire and allows you other ways to communicate.

Mechanical Properties and Uses
- The usual size is about 145 × 165 × 72 mm (H × W × D) and the weight is about 0.5–0.7 kg, depending on the source. It can be mounted in control cabinets with Series C hardware.
- The FC-RUSIO-3224 is used a lot in industries that need remote, safety-rated I/O to keep an eye on field devices and operate final elements like valves, motors, and safety interlocks. These include process automation, oil and gas, chemical plants, power production, and more.
Capabilities for I/O
- All 32 channels are “universal safe,” which means that each one can be set up as a digital input (with or without line monitoring), a digital output (with line monitoring), an analog input (0–20mA or 4–20mA active), or an analog output (0–20mA or 4–20mA active).
- The module can handle up to 32 digital inputs and outputs, 32 analog inputs and outputs, and a total of around 9 A on the outputs.
- You can set up Channel 32 as an Emergency Shutdown (ESD) function channel for safety-related trips in important situations.
Part Number Cross-References
- Honeywell Model: FC-RUSIO-3224
- Alternative Designation: RUSIO-3224
- Safety Manager Material Code: 51307171-series reference paths (depending on exact bundled IOTA kits).
Safety, Communication, and Diagnostics
- Even when just one channel is used, the FC-RUSIO-3224 meets SIL 3 standards. It can accomplish this because it contains a backup CPU, built-in watchdogs, and a method to keep track of the temperature.
- Putting two modules together makes things even more pointless. The module sends messages to the Safety Manager controller over two 100 Mbit Ethernet-based Safety Manager universal I/O lines that travel through specific switches.
- This makes sure that the message is clear and gets the point across. Self-diagnostics, line and loop monitoring, a real-time clock for sequence-of-events (SOE) time-stamping with 1 ms resolution, and front-panel LEDs for power and health make it easy to find and fix problems.
Data on the environment and electricity
- Power supply: 24 V DC (typically between −15% and +30%), and the module can draw up to 300 mA of current without a field load. Most of the time, the module’s outer temperature range is between −40 °C and +70 °C.
- However, the electronics within can endure higher temperatures. The temperature range for storage is around −40 °C to +85 °C.
- The device has CE and other safety approvals and is safe to use in places with a lot of pollution (Pollution Degree 2 or higher). It may work without condensation in relative humidity ranges between 10% and 95%.
14 DAYS RETURN POLICY
RETURNS ARE ACCEPTED IN 14 DAYS. BUYER PAYS THE SHIPPING CHARGES. RESTOCKING FEES 20%.
NOTE:
IF THE ITEM COMES UNDER CUSTOMS, THE BUYER WILL BE FULLY RESPONSIBLE FOR DUTIES AND OTHER CHARGES. WE, AS THE SELLER, DO NOT ACCEPT RETURNS OR REFUNDS IN THIS CASE. KINDLY CONNECT WITH US BEFORE PURCHASING AN ITEM OR IF YOU HAVE ANY OTHER QUERIES.
FEEDBACK
WE WILL BE WAITING FOR YOUR VALUABLE FEEDBACKS. THANK YOU FOR SHOWING TRUST IN US.
100% Genuine Products
-> YOU WILL GET WHAT YOU SEE IN PHOTOS
-> UNDERSTAND THE PRODUCT BEFORE BUYING
PACKAGING
QUALITY PACKING FOR EACH PRODUCT. ASSURED SAFE & UNDAMAGED DELIVERY.
SHIPPING
FeDEX, DHL EXPRESS INTERNATIONAL SHIPPING.
TAXES & IMPORT DUTIES
DESTINATION COUNTRY ALL TAXES & DUTY TO BE PAID BY BUYER (NOT INCLUDED IN PRICE.