Honeywell CC-PCF901 51405047-176 Control Firewall Module

Description

NEW HONEYWELL CC-PCF901 CONTROL FIREWALL MODULE 51405047-176

The Honeywell CC-PCF901 (Part Number: 51405047-176) is a Control Firewall (CF9) Module for the Experion Process Knowledge System (PKS) C Series architecture. This module acts as the communications centre for Fault Tolerant Ethernet (FTE) networks, and is designed to ensure that essential industrial control processes are shielded from network traffic bottlenecks, unauthorised data packets and cyber vulnerabilities.

The CC-PCF901 is designed for rugged industrial applications and provides an efficient way of delivering FTE connectivity to in-cabinet network nodes such as C300 Controllers and Series C Input / Output Modules. It shields essential control networks from larger plant networks, preventing hostile or non-critical Ethernet traffic from interfering with deterministic process automation.

 

Model details

  • Model Number: CC-PCF901
  • Manufacturer Part Number (MPN): 51405047-176
  • Product Type: Control Firewall C9 Module (CF9)
  • Associated Termination Assembly: Mounts on the CC-TCF901 or DC-TCF901 Input/Output Termination Assembly (IOTA)

Honeywell CC-PCF901 Series C Control Firewall front panel showing power status LEDs and 1 to 8 Ethernet port channels. Honeywell CC-PCF901 Control Firewall Module 51405047-176 technical label showing product serial number and certifications.

Product Datasheet and Installation Manual

Download PDF File

 

Technical details

Parameter Specifications
Manufacturer Honeywell
Model / Part Number CC-PCF901 / 51405047-176
Architecture Platform Experion PKS Series C / Experion LX
Port Configuration 9 Ports (8 Downlink Ports for FTE + 1 Uplink Port to Level 2)
Supply Voltage Rating 24 VDC plus or minus 10 percent
Current Consumption 195 mA Nominal / Power consumption approx 10 W
Operating Temperature -40 to +85 degrees Celsius (Industrial Grade)
Relative Humidity 5 to 95 percent RH Non-condensing
Vibration / Shock Resistance 5g Peak at 20-500 Hz / 30g Peak for 11 ms
Coating Protection G3 Conformal Coating (Standard for corrosive environments)
Dimensions (H x W x D) 23.8 cm x 13.5 cm x 2.0 cm
Net Weight 0.24 kg / 0.53 lbs

 

Compatibility Data

Compatible Component Model / Part Number Role within Architecture Compatibility Notes
Control Firewall IOTA CC-TCF901 / DC-TCF901 Input/Output Termination Assembly Required carrier base for physical mounting and external wiring termination.
C300 Controller CC-PCNT01 / CC-PCNT02 Central Processing Node Connects directly via downlink FTE ports for dedicated, firewall-protected control traffic.
Series C I/O Modules CC-PFB401 / CC-PAIH01 / etc. Process Input / Output Nodes Interfaced directly via downlink channels to handle field instrumentation loop commands.
FTE Bridge Module CC-TFB401 / CC-FIMB01 Fieldbus Network Interface Bridges local foundation fieldbus traffic into the secure FTE loop managed by the CF9 module.
Experion Software Release R300 through R5xx System Control Software Fully compatible across multiple legacy and contemporary Experion PKS system releases.

 

Expert Engineer’s Guide By NDMarineTech:

  1. POST Diagnostic Verification: During startup or a hot-swap replacement, watch the module’s LEDs closely. The Power LED should instantly turn green, followed by a brief red indicator on the Status LED. This red light means the Power-On Self Test (POST) is actively running. Once it finishes successfully, it changes to steady green, and the FTE port lights will begin blinking as traffic routes.
  2. Handle with Care During Hot Swapping: While the CC-PCF901 supports online replacement without removing the underlying CC-TCF901 IOTA base, always ground yourself with an ESD wrist strap before handling. Onboard environments are highly prone to static buildup, and protecting the delicate rear backplane pins keeps the internal circuitry safe.
  3. Inspect the IOTA Pins: If you are swapping an old module out for this new unit due to unexpected connection drops, take a bright light and inspect the IOTA carrier pins for signs of salt-air corrosion or oxidation before clicking the new module into place.
Shipping and Delivery

30 DAYS RETURN POLICY

RETURNS ACCEPTED IN 30 DAYS. BUYER PAYS THE SHIPPING CHARGES. RESTOCKING FEES 20%.

NOTE:

IF THE ITEM COMES UNDER CUSTOMS, THE BUYER WILL BE FULLY RESPONSIBLE FOR DUTIES & OTHER CHARGES. WE AS A SELLER DO NOT ACCEPT THE RETURN AND REFUND IN THIS CASE. KINDLY CONNECT WITH US BEFORE PURCHASING AND ITEM OR IF YOU HAVE ANY OTHER QUERIES.

FEEDBACK

WE WILL BE WAITING FOR YOUR VALUABLE FEEDBACKS. THANK YOU FOR SHOWING TRUST IN US.

100% Genuine Products

-> YOU WILL GET WHAT YOU SEE IN PHOTOS

-> UNDERSTAND THE PRODUCT BEFORE BUYING

PACKAGING

QUALITY PACKING FOR EACH PRODUCT. ASSURED SAFE & UNDAMAGED DELIVERY.

SHIPPING

FeDEX, DHL EXPRESS INTERNATIONAL SHIPPING.

TAXES & IMPORT DUTIES

DESTINATION COUNTRY ALL TAXES & DUTY TO BE PAID BY BUYER (NOT INCLUDED IN PRICE.